Emerson 8750-CA-NS丨PAC8000 Controller Carrier with power丨8750-CA-NS-03
PAC8000 PAC8000 Universal Node Services Carrier
item no.:
KJ3002X1-BA1lead time:
1-2 daysproduct orgin:
The USAshipping port:
Xiamenpayment:
T/TCondition:
NEWEmerson KJ3002X1-BA1 Power Specifications
Emerson KJ3002X1-BA1 Environmental Specifications
Emerson KJ3002X1-BA1 Removal and Insertion
An I/O loop assessment must be complete on all energy limited nodes.Field power supplied to this device, either at the field terminal or as bussed field power through the carrier, must be removed before removing or connecting the device.
An I/O loop assessment must be complete on all energy limited nodes.
This unit may be removed or inserted while system power is energized under the following conditions: (Note Only one unit at a time may be removed with system power energized.)
When used with KJ1501X1-BC1 System Dual DC/DC Power Supply operating on 24 VDC or 12 VDC input power. The primary circuit wiring inductance for input power must be less than 23 uH, or a certified supply with an open circuit voltage, Ui of 12.6 VDC and an Lo of less than 23 uH (including wire inductance).
A rotary keying system ensures compatibility between I/O cards and terminal blocks after installation is complete. The terminal block must have the keys set for the I/O card with which it is to be used.
A terminal block fuse may NOT be removed with field power energized for non-sparking circuits.
This unit contains no user serviceable parts and should not be disassembled for any reason.
Calibration is not required.
Emerson KJ3002X1-BA1 Datasheet Download
To get lowest price with best original quality,pls don`t hesitate to leave a message here.Thank you!