NewIS200TICIH2ACB Specifications
Number of channels: 24 input channels for isolated voltage sensing
Fault detection in
I/O board: Non-responding contact input in test mode
Unplugged cable or failed ID chip
Physical
Size 17.8 cm x 33.02 cm
Temperature Operating -30 to +65ºC (-22 to +149 ºF)
The Contact Input with Point Isolation IS200TICIH2ACB terminal board provides 24 point isolated voltage detection circuits to sense a range of voltages across relay contacts, fuses, and switches.
In the Mark* VI system, the IS200TICIH2ACB is controlled by the VCCC board and supports simplex and TMR applications. Cables with molded plugs connect IS200TICIH2ACB to the VME rack where the I/O boards are mounted.
In the Mark VIe system, the IS200TICIH2ACB works with the PDIA I/O pack and supports simplex, dual, and TMR applications. One, two, or three PDIAs plug into the IS200TICIH2ACB to support a variety of system configuration
Connect the wires for the 24 isolated digital inputs directly to two I/O terminal blocks on the terminal board. These blocks are held down with two screws and can be unplugged from the board for maintenance. Each block has 24 terminals accepting up to #12 AWG wires. A shield terminal strip attached to chassis ground is located immediately to the left of each terminal block.
In a simplex system, connect TICI to the I/O processor using connector JR1. In a TMR system, connect TICI to the I/O processors using connectors JR1, JS1, and JT1. Cables or I/O packs are plugged in depending on the type of Mark VI or Mark VIe system, and the level of redundancy.
The IS200TICIH2ACB is similar to TBCI, except for the following items:
• No contact excitation is provided on the terminal board.
• Each input is electrically isolated from all others and from the active electronics.
There are two groups of the IS200TICIH2ACB with different nominal voltage thresholds. TICIH1 has the following input voltage ranges:
• 70-145 V dc, nominal 125 V dc, with a detection of 39 to 61 V dc
• 200-250 V dc, nominal 250 V dc, with a detection of 39 to 61 V dc
• 90-132 V rms, nominal 115 V rms, 47-63 Hz, with a detection of 35 to 76 V ac
• 190-264 V rms, nominal 230 V rms, 47-63 Hz, with a detection of 35 to 76 V ac
TICIH2 has the following input voltage range:
• 16-32 V dc, nominal 24 V dc, with a detection threshold of 9.5 to 15 V dc TICI provides input hardware filtering with time delays of 15 ms, nominal:
• For dc applications the time delay is 15 ±8 ms
• For ac applications the time delay is 15 ±13 ms
In addition to hardware filters, the contact input state is software-filtered, using configurable time delays selected from 0, 10, 20, 50, and 100 ms. For ac inputs, a filter of at least 10 ms is recommended.