GE Fanuc IC698CPE010 Processor Module CPU
GE Fanuc IC698CPE010 Processor Module CPU 100% Brand New. 365 days warranty.
item no.:
IS200SPROH1Alead time:
5-7 DAYSproduct orgin:
USAshipping port:
XIAMEN, CHINApayment:
T/Tcolor:
DEPENDING ON THE MATERIALGE IS200SPROH1A Emergency Protection Functional Description
- Part Number: IS200SPROH1A
- Manufacturer: General Electric
- Series: Mark VIe
- Number of relay channels: 12
- Product Type: Backup Protection Terminal Board
- Generator and bus voltage sensors: 2
- Magnetic speed pickup pulse rate range: 2Hz
- Power Requirements: +5 V dc, 6 A
- Power supply voltage: 24 V dc
- Magnetic speed pickup sensitivity: 27 mV
- Mounting: DIN-rail mounting
- Technology: Surface mount
- Operating temperature: 30 to 65°C
- Size: 15.9 cm high x 17.8 cm
- Availability: In Stock
- Country of Origin: USA
The Emergency Protection (SPRO) terminal board hosts a PPRO I/O pack. It conditions speed signal inputs for the PPRO and contains a pair of potential transformers (PTs) for bus and generator voltage input. It has a DC-37 pin connector adjacent to the PPRO pack connector that accepts a cable leading to a Mark* VIe backup trip relay terminal board.
• IS200SPROH1A features 24 barrier terminals in a pluggable block.
• IS200SPROH2A features 24 pluggable Euro-style box terminals.
The SPRO and a plastic insulator mount on a sheet metal carrier, which mounts on a DIN-rail. Optionally, the SPRO and insulator mount on a sheet metal assembly,which bolts directly in a panel. Speed signals and PT inputs are wired directly to the terminal block using typical #18 AWG wires.
The SPROH1A barrier terminal block is removable for board replacement. The SPROH2A Euro-Block type terminal block has terminals that can be removed for board replacement.
The PPRO I/O pack mounts directly on connector JA1 of the SPRO. A DC-37 pin conductor cable plugs into connector JA3 of SPRO with the other end attached to the selected backup trip terminal board.
In the following drawing, the PT inputs to SPRO are shown on terminals 1-4. Three speed inputs are shown on terminals 19-24. Terminals 7-15 are reserved for future control feature expansion and are routed to the JA1 PPRO connector. Terminals 5-6 and 16-18 have no board connection. The JA1 and JA3 connectors provide locations for PPRO and the trip terminal board cable.
To get lowest price with best original quality,pls don`t hesitate to leave a message here.Thank you!